| ≥1 piece |
Main Parameters of the set
The model of the unit: JHS-300GF
Power: 300KW/375kVA
Rated voltage: 400V/230V
Rated current: 540A
Rated frequency: 50Hz
The factor of rated power COS=0.8(lag)
The regulating rate of instantaneous voltage: ≤ -15%/ +20%
The time of steady voltage: ≤ 1.5sec
The waving rate of voltage: ≤ 0.5%
The regulating rate of steady frequency: ≤ 3%
The regulating rate of instantaneous frequency: ≤ 10%
The time of steady frequency: 3sec
The waving rate of frequency: ≤ 0.25%
The waste of fuel with full load: 225g/kwh
Size(mm): 3000*1400*1800
Weight: 3000KG
1. The main parameters of the diesel engine
Model: 12V135AZD
Spare Power: 412kVA /330KW
Type: Four strokes, waste gas turbine boost, direct spurting type
Cooling way: Water cooling
With Type: V type
Bore *Trip: 135 mm*150 mm
Displacement 26.8L
Lubricating oil capacity: 57L
Cylinder: 12cylinders
Rotating speed: 1500r/min
The regulation of rotating speed: Mechanical speed regulator
Starting way: DC24V\ starting with electricity
2. The main parameters of the generator
Model: KU-300-4
Type: Brushless (AVR automatic voltage regulating)
The connecting way of the phase: Three phases four lines
Insulation degree: H degree
Grading Protection: IP22
The components of the set
1)Diesel engine
2)Generator
3)Seperating screen
Controlling Screen
The controlling screen is Ordinary integrative type controlling screen, with three-phase voltage, frequency and three-phase current, oil pressure, coolant
Capacity: 30KW to 2000KW